Fundamentals of Distance Protection



《Fundamentals of Distance Protection》由会员分享,可在线阅读,更多相关《Fundamentals of Distance Protection(111页珍藏版)》请在装配图网上搜索。
1、Click to edit Master text styles,,Click to edit Master text styles,,Second level,,Third level,,Fourth level,,Fifth level,,111,/,,GE /,,20 September 2024,Fundamentals of Distance Protection,GE Multilin,Outline,Transmission line introduction,,What is distance protection?,,Non-pilot and pilot schemes,,
2、Redundancy considerations,,Security for dual-breaker terminals,,Out-of-step relaying,,Single-pole tripping,,Series-compensated lines,,Transmission Lines,A Vital Part of the Power System,:,,,Provide path to transfer power between generation and load,,Operate at voltage levels from 69kV to 765kV,,Dere
3、gulated markets, economic, environmental requirements have pushed utilities to operate transmission lines close to their limits.,Transmission Lines,Classification of line length depends on:,,Source-to-line Impedance Ratio (SIR), and,,Nominal voltage,,Length considerations:,,Short Lines: SIR > 4,,Med
4、ium Lines: 0.5 < SIR < 4,,Typical Protection Schemes,Short Lines,Current differential,,Phase comparison,,Permissive Overreach Transfer Trip (POTT),,Directional Comparison Blocking (DCB),Typical Protection Schemes,Medium Lines,Phase comparison,,Directional Comparison Blocking (DCB),,Permissive,Underr
5、each,Transfer Trip (PUTT),,Permissive Overreach Transfer Trip (POTT),,Unblocking,,Step Distance,,Step or coordinated,overcurrent,,Inverse time,overcurrent,,Current Differential,Typical Protection Schemes,Long Lines,Phase comparison,,Directional Comparison Blocking (DCB),,Permissive,Underreach,Transf
6、er Trip (PUTT),,Permissive Overreach Transfer Trip (POTT),,Unblocking,,Step Distance,,Step or coordinated,overcurrent,,Current Differential,,What is distance protection?,For internal faults:,,IZ – V,and,V,approximately in phase (,mho,),,IZ – V,and,IZ,approximately in phase (,reactance,),RELAY (,V,I,
7、),IntendedREACH point,Z,F,1,I*Z,V=I*Z,F,I*Z - V,What is distance protection?,For external faults:,,IZ – V,and,V,approximately out of phase (,mho,),,IZ – V,and,IZ,approximately out of phase (,reactance,),RELAY (,V,I,),IntendedREACH point,Z,I*Z,V=I*Z,F,I*Z - V,F,2,What is distance protection?,RELAY
8、,IntendedREACH point,Z,Source Impedance Ratio, Accuracy & Speed,Line,System,Relay,Voltage at the relay:,,Fault location,Voltage (%),Voltage change (%),75%,88.24,2.76,90%,90.00,0.91,100%,90.91,N/A,110%,91.67,0.76,Source Impedance Ratio, Accuracy & Speed,,Line,System,Relay,Voltage at the relay:,Consi
9、der SIR = 30,Fault location,Voltage (%),Voltage change (%),75%,2.4390,0.7868,90%,2.9126,0.3132,100%,3.2258,N/A,110%,3.5370,0.3112,Challenges in relay design,Transients:,,High frequency,,DC offset in currents,,CVT transients in voltages,CVT output,0,1,2,3,4,steady-state,output,power cycles,-30,-20,-1
10、0,0,10,20,30,voltage, V,Challenges in relay design,Transients:,,High frequency,,DC offset in currents,,CVT transients in voltages,CVT,output,0,1,2,3,4,steady-state,output,-60,-40,-20,0,20,40,power cycles,voltage, V,60,Challenges in relay design,-0.5,0,0.5,1,1.5,-100,-50,0,50,100,Reactance comparator
11、 [V],power cycles,S,POL,S,OP,Sorry… Future (unknown),In-phase = internal fault,,Out-of-phase = external fault,Transient Overreach,Fault current generally contains dc offset in addition to ac power frequency component,,Ratio of dc to ac component of current depends on instant in the cycle at which fa
12、ult occurred,,Rate of decay of dc offset depends on system X/R,Zone 1 and CVT Transients,Capacitive Voltage Transformers (CVTs) create certain problems for fast distance relays applied to systems with high Source Impedance Ratios (SIRs):,,CVT-induced transient voltage components may assume large mag
13、nitudes (up to 30-40%) and last for a comparatively long time (up to about 2 cycles),,60Hz voltage for faults at the relay reach point may be as low as 3% for a SIR of 30,,the signal may be buried under noise,,CVT transients can cause distance relays to overreach. Generally, transient overreach may
14、be caused by:,,overestimation of the current (the magnitude of the current as measured is larger than its actual value, and consequently, the fault appears closer than it is actually located),,,underestimation of the voltage (the magnitude of the voltage as measured is lower than its actual value),,
15、combination of the above,,Zone 1 and CVT Transients,Distance Element Fundamentals,XL,XC,R,Z1,End Zone,Impedance locus may pass,,below the origin of the Z-plane -,,this would call for a time delay,,to obtain stability,apply delay (fixed or adaptable),,reduce the reach,,adaptive techniques and better
16、filtering algorithms,CVT Transient Overreach Solutions,Optimize signal filtering:,,currents - max 3% error due to the dc component,,voltages - max 0.6% error due to CVT transients,,Adaptive double-reach approach,,filtering alone ensures maximum transient overreach at the level of 1% (for SIRs up to
17、5) and 20% (for SIRs up to 30),,to reduce the transient overreach even further an adaptive double-reach zone 1 has been implemented,CVT Transients – Adaptive Solution,The outer zone 1:,,is fixed at the actual reach,,applies certain security delay to cope with CVT transients,The inner zone 1:,,has it
18、s reach dynamically controlled by the voltage magnitude,,is instantaneous,CVT Transients – Adaptive Solution,Desirable Distance Relay Attributes,Filters,:,,Prefiltering of currents to remove dc decaying transients,,Limit maximum transient overshoot (below 2%),,Prefiltering of voltages to remove low
19、frequency transients caused by CVTs,,Limit transient overreach to less than 5% for an SIR of 30,,Accurate and fast frequency tracking algorithm,,Adaptive reach control for faults at reach points,,Distance Relay Operating Times,Distance Relay Operating Times,20ms,15ms,25ms,30ms,35ms,Distance Relay Op
20、erating Times,SLG faults,LL faults,3P faults,Actual maximum reach curves,Relay 1,Relay 3,Relay 2,Relay 4,Maximum Torque Angle,Angle at which mho element has maximum reach,,Characteristics with smaller MTA will accommodate larger amount of arc resistance,Traditional,Directional angle lowered and “sla
21、mmed”,Directional angle “slammed”,Both MHO and directional angles “slammed” (lens),Mho Characteristics,Typical load characteristic impedance,,+R,Operate,,area,No Operate area,+X,L,+ = LOOKING INTO LINE normally considered forward,,Load Trajectory,Reach,Load Swings,Load swing,“Lenticular” Characteris
22、tic,Load Swings,Load Encroachment Characteristic,The load encroachment element responds to positive sequence voltage and current and can be used to block phase distance and phase overcurrent elements.,Blinders,Blinders limit the operation of distance relays (quad or mho) to a narrow region that para
23、llels and encompasses the protected line,,Applied to long transmission lines, where mho settings are large enough to pick up on maximum load or minor system swings,Quadrilateral Characteristics,Ground Resistance (Conductor falls on ground),XL,R,Resultant impedance outside of the mho operating region
24、,Quadrilateral Characteristics,Mho,Quadrilateral,Better coverage for ground faults due to resistance added to return path,Lenticular,Used for phase elements with long heavily loaded lines heavily loaded,Standard for phase elements,JX,R,Distance Characteristics - Summary,Distance Element Polarization
25、,The following polarization quantities are commonly used in distance relays for determining directionality:,,Self-polarized,,Memory voltage,,Positive sequence voltage,,,Quadrature,voltage,,Leading phase voltage,Memory Polarization,Positive-sequence memorized voltage is used for polarizing:,,Mho comp
26、arator (dynamic, expanding Mho),,Negative-sequence directional comparator (Ground Distance Mho and Quad),,Zero-sequence directional comparator (Ground Distance MHO and QUAD),,Directional comparator (Phase Distance MHO and QUAD),,Memory duration is a common distance settings (all zones, phase and gro
27、und, MHO and QUAD),,,Memory Polarization,,,jX,R,Dynamic MHO characteristic for a reverse fault,Dynamic MHO characteristic for a forward fault,Impedance During Close-up Faults,Static MHO characteristic (memory not established or expired),Z,L,Z,S,Memory Polarization,Memory Polarization…Improved Resist
28、ive Coverage,Dynamic MHO characteristic for a forward fault,Static MHO characteristic (memory not established or expired),,,jX,R,Z,L,Z,S,R,L,Choice of Polarization,In order to provide flexibility modern distance relays offer a choice with respect to polarization of ground,overcurrent,direction funct
29、ions:,,Voltage polarization,,Current polarization,,Dual polarization,,Ground Directional Elements,Pilot-aided schemes using ground mho distance relays have inherently limited fault resistance coverage,,Ground directional over current protection using either negative or zero sequence can be a useful
30、supplement to give more coverage for high resistance faults,,Directional discrimination based on the ground quantities is,fast,:,,Accurate angular relations between the zero and negative sequence quantities establish very quickly because:,,During faults zero and negative-sequence currents and voltag
31、es build up from very low values (practically from zero),,The pre-fault values do not bias the developing fault components in any direction,Distance Schemes,Pilot Aided Schemes,No Communication between Distance Relays,Communication between Distance relays,Non-Pilot Aided Schemes,,(Step Distance),Ste
32、p Distance Schemes,,Zone 1:,,Trips with no intentional time delay,,Underreaches,to avoid unnecessary operation for faults beyond remote terminal,,Typical reach setting range 80-90% of Z,L,,Zone 2:,,Set to protect remainder of line,,Overreaches into adjacent line/equipment,,Minimum reach setting 120%
33、 of Z,L,,Typically time delayed by 15-30 cycles,,Zone 3:,,Remote backup for relay/station failures at remote terminal,,Reaches beyond Z2, load encroachment a consideration,BUS,BUS,Z1,Z1,Local,Remote,Step Distance Schemes,BUS,BUS,Z1,Z1,End Zone,End Zone,Local,Remote,Step Distance Schemes,BUS,Z1,Z1,Br
34、eaker Tripped,BUS,Breaker Closed,Local,Remote,Step Distance Schemes,BUS,Z1,Z1,BUS,Z2 (time delayed),Remote,Local,Step Distance Schemes,Z2 (time delayed),BUS,Z1,BUS,Z2 (time delayed),Step Distance Schemes,Z3 (remote backup),…,Step Distance Protection,Local Relay – Z2,,,Zone 2 PKP,Local Relay,Remote
35、Relay,Remote Relay – Z4,,Zone 4 PKP,,,Over Lap,,,Distance Relay Coordination,BUS,BUS,Communication Channel,Local Relay,Remote Relay,Need For Pilot Aided Schemes,Pilot Communications Channels,Distance-based pilot schemes traditionally utilize simple on/off communications between relays, but can also
36、utilize peer-to-peer communications and GOOSE messaging over digital channels,,Typical communications media include:,,Pilot-wire (50Hz, 60Hz, AT),,Power line carrier,,Microwave,,Radio,,Optic fiber (directly connected or multiplexed channels),Distance-based Pilot Protection,Pilot-Aided Distance-Based
37、 Schemes,,DUTT,– Direct Under-reaching Transfer Trip,,,PUTT,– Permissive Under-reaching Transfer Trip,,,POTT,– Permissive Over-reaching Transfer Trip,,,Hybrid POTT,– Hybrid Permissive Over-reaching Transfer Trip,,,DCB,– Directional Comparison Blocking Scheme,,,DCUB,– Directional Comparison Unblockin
38、g Scheme,Direct Underreaching Transfer Trip (DUTT),Requires only,underreaching,(RU) functions which overlap in reach (Zone 1).,,Applied with FSK channel,,GUARD frequency transmitted during normal conditions,,TRIP frequency when one RU function operates,,Scheme does not provide tripping for faults be
39、yond RU reach if remote breaker is open or channel is inoperative.,,Dual pilot channels improve security,,,,,,Bus,Line,Bus,Zone 1,Zone 1,DUTT Scheme,Permissive Underreaching Transfer Trip (PUTT),Requires both under (RU) and overreaching (RO) functions,,Identical to DUTT, with pilot tripping signal s
40、upervised by RO (Zone 2),,&,Local Trip,Zone 2,Rx PKP,OR,Zone 1,PUTT Scheme,Permissive Overreaching Transfer Trip (POTT),Requires overreaching (RO) functions (Zone 2).,,Applied with FSK channel:,,GUARD frequency sent in stand-by,,TRIP frequency when one RO function operates,,No trip for external faul
41、ts if pilot channel is inoperative,,Time-delayed tripping can be provided,,,POTT Scheme,POTT Scheme,POTT – Permissive Over-reaching Transfer Trip,BUS,BUS,End Zone,Communication Channel,Local,Relay,Remote,Relay,Remote Relay FWD I,GND,Ground Dir OC Fwd,OR,Local Relay – Z2,,ZONE 2 PKP,Local Relay FWD
42、 I,GND,Ground Dir OC Fwd,OR,TRIP,Remote Relay – Z2,POTT TX,ZONE 2 PKP,POTT RX,Communication Channel,POTT Scheme,POTT TX 4,POTT TX 3,POTT TX 2,POTT TX 1,A to G,B to G,C to G,Multi Phase,Local Relay,Remote Relay,POTT RX 4,POTT RX 3,POTT RX 2,POTT RX 1,Communications Channel(s),POTT Scheme,Local
43、Relay,Remote Relay,POTT TX,ZONE 2 OR,,GND DIR OC FWD,Communication Channel,TRIP,GND DIR OC REV,GND DIR OC REV,POTT RX,Start Timer,Timer Expire,GND DIR OC FWD,POTT Scheme,,Current reversal example,Local Relay,Open,Remote Relay,Remote FWD I,GND,POTT TX,Remote – Z2,Communication Channel,POTT
44、 RX,OPEN,POTT TX,Communication Channel,POTT RX,TRIP,POTT Scheme,,Echo example,Hybrid POTT,Intended for three-terminal lines and weak,infeed,conditions,,Echo feature adds security during weak,infeed,conditions,,Reverse-looking distance and,oc,elements used to identify external faults,Hybrid POTT,D
45、irectional Comparison Blocking (DCB),Requires overreaching (RO) tripping and blocking (B) functions,,ON/OFF pilot channel typically used (i.e., PLC),,Transmitter is keyed to ON state when blocking function(s) operate,,Receipt of signal from remote end blocks tripping relays,,Tripping function set wi
46、th Zone 2 reach or greater,,Blocking functions include Zone 3 reverse and low-set ground,overcurrent,elements,DCB Scheme,BUS,BUS,End Zone,Communication Channel,Directional Comparison Blocking (DCB),,Directional Comparison Blocking (DCB),,Internal Faults,,Local Relay,Remote Relay,Local Relay – Z2,,Zo
47、ne 2 PKP,TRIP Timer Start,FWD I,GND,,GND DIR OC Fwd,OR,Dir Block RX,NO,TRIP,Expired,Local Relay,Remote Relay,Remote Relay – Z4,,Zone 4 PKP,REV I,GND,GND DIR OC Rev,OR,DIR BLOCK TX,Local Relay – Z2,,,Zone 2 PKP,Dir Block RX,Communication Channel,FWD I,GND,,GND DIR OC Fwd,OR,TRIP Timer Start,No TRI
48、P,Directional Comparison Blocking (DCB),,External Faults,,Directional Comparison Unblocking (DCUB),Applied to Permissive Overreaching (POR) schemes to overcome the possibility of carrier signal attenuation or loss as a result of the fault,,Unblocking provided in the receiver when signal is lost:,,If
49、 signal is lost due to fault, at least one permissive RO functions will be picked up,,Unblocking logic produces short-duration TRIP signal (150-300 ms). If RO function not picked up, channel lockout occurs until GUARD signal returns,,,,,DCUB Scheme,BUS,BUS,End Zone,Communication Channel,Directional
50、Comparison Unblocking (DCUB),,Directional Comparison Unblocking (DCUB),,Normal conditions,,Local Relay,Remote Relay,GUARD1 TX,GUARD1 RX,Communication Channel,GUARD2 TX,GUARD2 RX,NO Loss of Guard,FSK Carrier,FSK Carrier,NO Permission,NO Loss of Guard,NO Permission,Load Current,Directional Compariso
51、n Unblocking (DCUB),,Normal conditions, channel failure,,Local Relay,Remote Relay,GUARD1 TX,GUARD1 RX,Communication Channel,GUARD2 TX,GUARD2 RX,FSK Carrier,FSK Carrier,Loss of Guard,Block Timer Started,Loss of Guard,Block Timer Started,Load Current,NO RX,NO RX,Block DCUB until Guard OK,Expired,Bl
52、ock DCUB until Guard OK,Expired,Loss of Channel,Directional Comparison Unblocking (DCUB),,Internal fault, healthy channel,,Local Relay,Remote Relay,GUARD1 TX,GUARD1 RX,Communication Channel,GUARD2 TX,GUARD2 RX,FSK Carrier,FSK Carrier,Loss of Guard,Permission,TRIP1 TX,Local Relay – Z2,,,Zone 2 PKP
53、,TRIP1 RX,TRIP2 TX,TRIP,Remote Relay – Z2,ZONE 2 PKP,TRIP Z1,TRIP2 RX,Directional Comparison Unblocking (DCUB),,Internal fault, channel failure,,Local Relay,Remote Relay,GUARD1 TX,GUARD1 RX,Communication Channel,GUARD2 TX,GUARD2 RX,FSK Carrier,FSK Carrier,TRIP1 TX,Local Relay – Z2,,,Zone 2 PKP,
54、NO RX,TRIP2 TX,TRIP,Remote Relay – Z2,ZONE 2 PKP,TRIP Z1,NO RX,Loss of Guard,,Loss of Channel,Loss of Guard,Block Timer Started,Duration Timer Started,Expired,Redundancy Considerations,,Redundant protection systems increase dependability of the system:,,Multiple sets of protection using,same prote
55、ction principle,and multiple pilot channels overcome individual element failure,,or,,Multiple sets of protection using,different protection principles,and multiple channels protects against failure of one of the protection methods.,,Security can be improved using “voting” schemes (i.e., 2-out-of-3),
56、 potentially at expense of dependability.,,Redundancy of instrument transformers, battery systems, trip coil circuits, etc. also need to be considered.,BUS,BUS,End Zone,Communication Channel 1,Communication Channel 2,Loss of Channel 2,AND Channels:,POTT Less Reliable,DCB Less Secure,OR Channels:,POT
57、T More Reliable,DCB More Secure,More Channel Security,More Channel Dependability,Redundant Communications,Redundant Pilot Schemes,Integrated functions:,,weak,infeed,,echo,,line pick-up (SOTF),,Basic protection elements used to key the communication:,,distance elements,,fast and sensitive ground (zer
58、o and negative sequence) directional,IOCs,with current, voltage, and/or dual polarization,Pilot Relay Desirable Attributes,Pre-programmed distance-based pilot schemes:,,Direct Under-reaching Transfer Trip (DUTT),,Permissive Under-reaching Transfer Trip (PUTT),,Permissive Overreaching Transfer Trip (
59、POTT),,Hybrid Permissive Overreaching Transfer Trip (HYB POTT),,Blocking scheme (DCB),,Unblocking scheme (DCUB),,Pilot Relay Desirable Attributes,Security for dual-breaker terminals,Breaker-and-a-half and ring bus terminals are common designs for transmission lines.,,Standard practice has been to:,,
60、sum currents from each circuit breaker externally by paralleling the,CTs,,use external sum as the line current for protective relays,,For some close-in external fault events, poor CT performance may lead to improper operation of line relays.,Security for dual-breaker terminals,Accurate CTs preserve
61、the reverse current direction under weak remote infeed,Security for dual-breaker terminals,Saturation of CT1 may invert the line current as measured from externally summated CTs,Security for dual-breaker terminals,Direct measurement of currents from both circuit breakers allows the use of supervisor
62、y logic to prevent distance and directional,overcurrent,elements from operating incorrectly due to CT errors during reverse faults.,,Additional benefits of direct measurement of currents:,,independent BF protection for each circuit breaker,,independent,autoreclosing,for each breaker,Security for dua
63、l-breaker terminals,Supervisory logic should:,,not affect speed or sensitivity of protection elements,,correctly allow tripping during evolving external-to-internal fault conditions,,determine direction of current flow through each breaker independently:,,Both currents in FWD direction, internal fa
64、ult,,One current FWD, one current REV, external fault,,allow tripping during all forward/internal faults,,block tripping during all reverse/external faults,,initially block tripping during evolving external-to-internal faults until second fault appears in forward direction. Block is then lifted to
65、permit tripping.,Single-pole Tripping,Distance relay must correctly identify a SLG fault and trip only the circuit breaker pole for the faulted phase.,,,Autoreclosing,and breaker failure functions must be initiated correctly on the fault event,,Security must be maintained on the healthy phases durin
66、g the open pole condition and any,reclosing,attempt.,Out-of-Step Condition,For certain operating conditions, a severe system disturbance can cause system instability and result in loss of synchronism between different generating units on an interconnected system.,Out-of-Step Relaying,Out-of-step blocking relays,,Operate in conjunction with mho tripping relays to prevent a terminal from tripping during severe system swings & out-of-step conditions.,,Prevent system from separating in an indiscrimi
- 温馨提示:
1: 本站所有资源如无特殊说明,都需要本地电脑安装OFFICE2007和PDF阅读器。图纸软件为CAD,CAXA,PROE,UG,SolidWorks等.压缩文件请下载最新的WinRAR软件解压。
2: 本站的文档不包含任何第三方提供的附件图纸等,如果需要附件,请联系上传者。文件的所有权益归上传用户所有。
3.本站RAR压缩包中若带图纸,网页内容里面会有图纸预览,若没有图纸预览就没有图纸。
4. 未经权益所有人同意不得将文件中的内容挪作商业或盈利用途。
5. 装配图网仅提供信息存储空间,仅对用户上传内容的表现方式做保护处理,对用户上传分享的文档内容本身不做任何修改或编辑,并不能对任何下载内容负责。
6. 下载文件中如有侵权或不适当内容,请与我们联系,我们立即纠正。
7. 本站不保证下载资源的准确性、安全性和完整性, 同时也不承担用户因使用这些下载资源对自己和他人造成任何形式的伤害或损失。
最新文档
- 36个关键词详解2025政府工作报告
- 学习2025年政府工作报告中的八大科技关键词
- 2025年政府工作报告要点速览接续奋斗共谱新篇
- 学习2025政府工作报告里的加减乘除
- 深化农村改革党课ppt课件(20250305)
- 弘扬雷锋精神凝聚奋进力量学习雷锋精神的丰富内涵和时代价值
- 深化农村改革推进乡村全面振兴心得体会范文(三篇)
- 2025年民营企业座谈会深度解读PPT课件
- 领导干部2024年述职述廉述责述学述法个人报告范文(四篇)
- 读懂2025中央一号党课ppt课件
- 2025年道路运输企业主要负责人安全考试练习题[含答案]
- 2024四川省雅安市中考英语真题[含答案]
- 2024湖南省中考英语真题[含答案]
- 2024宁夏中考英语真题[含答案]
- 2024四川省内江市中考英语真题[含答案]